Battery Settings
Setting battery-related parameters can optimize battery performance, extend battery life, and achieve intelligent charging and discharging strategies.
Charging Source Prority

The battery acquires power according to the set order.
By default priority, PV is placed before Grid, PV solar charges the battery first, Grid supplements the remaining charge.
In the negative electricity price scenario, Grid can be adjusted to be before PV.

Discharging Source Prority

Battery releases power according to the set order. The battery discharge priority can be configured based on the actual situation.

Battery Level Setting
1
Charge Cut-off SOC
Sets the capacity at which the battery pack stops charging.
2
Discharge Cut-off SOC
Sets the capacity at which the battery pack stops discharging.
Value 0 is not recommended for this parameter to avoid irreversible attenuation due to failure to charge the battery pack in time.
The priority is given to "Backup Capacity" in backup system wiring mode, while the parameter is applied in non-backup system wiring mode.
3
Peak shaving
Set the battery peak shaving cutoff point.
4
Backup Reserve SOC
You can set this parameter when a gateway exists in the system wiring.
In the on-grid scenario, the battery pack stops discharging when the backup capacity value is reached. In the off-grid scenario, the battery pack supplies power to power device and stops discharging when the Discharge Cut-off SOC setting is reached.
Users can manually set this parameter according to the power interruption frequency of their regions and leave time. Value 0 is not recommended for this parameter to avoid irreversible attenuation due to failure to charge the battery pack in time.
Battery Preheating scheduling

Pre-adjust the battery temperature to the optimal working range in low temperature environments to prevent performance degradation and safety hazards caused by low temperature.

1
Pack preheating
Set to to set the battery preheating period.
Battery Power Limit

If you need to set more detailed charging and discharging data, you can set this parameter.

1
Battery Max Charging Power
Set the maximum charging input power allowed by the battery.
2
Battery Max Discharging Power
Set the maximum discharging output power allowed by the battery.
Battery Automation

If this parameter is set, the battery will prioritize executing the parameters set by Battery Automation.

1
Add Time Period
Click to add Time Period.
2
Add your action
Click to add battery operation status.
Battery Charging
Maximum Charging Power: Set the maximum total input power allowed for the battery charging, including all charging sources.
Maximum Charging Power From grid to BAT: Set the maximum charging input power from Grid to BAT. This parameter must be ≤ Maximum Charging Power.
Battery Charging From Grid Cut-off SOC: When the battery SOC reaches this threshold, the grid is forced to stop charging the battery.
Battery Charging Source Priority: Adjust the battery energy source priority.
Battery Discharging
Maximum Discharging Power: Set the maximum total discharging output power allowed for the battery.
Maximum Discharging Power from BAT to Grid: Set the maximum discharging output power from BAT to Grid.This parameter must be ≤ Maximum Discharging Power.
Discharge Cut-off SOC from BAT to Grid: When the battery SOC reaches this threshold, the BAT is forced to stop transmitting power to the grid.
Battery Preserve: Maintain the current SOC without change.
Battery Self Consumption
Maximum Charging Power: Set the maximum charging input power from PV to the battery.
Maximum Discharging Power: Set the maximum discharging output power of the battery to the household load.
Last updated
Was this helpful?